Gerand Model K Fire Pump Test Meter

A calibrated venturi and attached GPM meter installed on the discharge of a fire pump to accurately determine pump performance 500 PSI (Buttweld, Grooved, 300# Flanged) and 275 PSI (150# Flanged)

Description

Gerand Model K Fire Pump Test Meter

A calibrated venturi and attached GPM meter installed on the discharge of a fire pump to accurately determine pump performance 500 PSI (Buttweld, Grooved, 300# Flanged) and 275 PSI (150# Flanged).

Attached to the meter with a brass chain is an oblong metal tag with the suggested piping diagram of the
system on one side, and the following operating instructions on the reverse side:

  • Close system OSY valve “A”
  • Open by-pass valve and “B” butterfly throttle valve
  • Purge meter, located on venturi, as follows:
    • a) Open station shut-off valves on venturi, and vent valves attached to meter.
      When a steady stream of water without air bubbles passes through the clear plastic hoses,
      the meter is purged of air.
    • b) Close the vent valves after purging.
  •  Start the fire pump, and read meter in GPM.
  • Refer to pump GPM requirement and adjust throttle valve to meet the requirement.
  • After the test, open valve “A” and close the by-pass and “B” valves.