Description
Firetrol FTA990 Disconnecting Devices provide a UL Listed means of disconnecting and isolating the fire pump controller from the incoming power source. The FTA990 gives overcurrent protection coordination upstream of the fire pump controller.
Overcurrent Protection Characteristics:
- The protective device shall NOT open with 2 minutes at 600% of the full load current of the fire pump motor(s).
- The protective device shall NOT open with a re-start transient of 24 times the full load current of the fire pump motor(s).
- The protective device shall NOT open within 10 minutes at 300% of the full load current of the fire pump motor(s).
- into for circuit breaker shall NOT adjustable.
Features
The following are included as standard with each controller:
- Suitable for use as service equipment
- NEMA Type 2 (IP22) Enclosure
- Flange mounted disconnect handle lockable in the “ON” position
Applications
The FTA990 shall be specifically designed to assure complete upstream overcurrent protection coordination with the electric fire pump controller. A flange mounted disconnect handle lockable in the closed (ON) position shall be standard.
Specifications
disconnecting means shall be a model FTA990, manufactured by Firetrol, Inc. The unit shall be factory assembled and tested. The FTA990 shall be specifically designed to assure complete upstream overcurrent protection co- ordination with the electric fire pump controller. A flange mounted disconnect handle lockable in the closed (ON) position shall be standard.
Standards, Listings & Approvals
- Suitable for use as service equipment
- UL Listed for fire pump service per:
- NFPA70 (National Electrical Code) 695.4(B) (2)(a)(2) – Normal Power Circuit
- NFPA70 (National Electrical Code) 695.4(B)(3)(c) – Markings
- NFPA70 (National Electrical Code) 695.3(F)(2) – Alternate Power Circuit
- NFPA20 (Standard for the Installation of Stationary Pumps for Fire Protection) 9.2.3.4.1
Enclosure
The components shall be housed in a NEMA Type 2 (IEC IP22) enclosure.
Overcurrent Protection Characteristics:
- The protective device shall NOT open within 2 minutes at 600% of the full load current of the
fire pump motor(s).
- The protective device shall NOT open with a re-start transient of 24 times the full load current
of the fire pump motor(s).
- The protective device shall NOT open within 10 minutes at 300% of the full load). for circuit breaker shall NOT be field adjustable.