Firetrol FTA200-A Alarm Panels

Firetrol FTA200 alarm panels are designed to meet the NFPA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended.

Description

Firetrol FTA200 alarm panels are designed to meet the NFPA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times.

Brand

Firetrol

Firetrol

Firetrol, was founded in the early 1970’s and incorporated in Erie, Pennsylvania by an entrepreneur who saw an opportunity in a unique marketplace; the fire pump control industry. The business grew steadily between 1971 and 1980 as the company developed the first fire pump controller with molded case circuit breakers which drastically reduced their size, the first manual wound rotor controller for the New York City high-rise marketplace, the first medium voltage controller, and the first UL Listed controller with an automatic power transfer switch.

Specifications

Alarm Panel
The main fire pump controller shall be a factory assembled, wired and tested unit.

Standards, Listings & Approvals
The controller shall conform to all the requirements of the latest editions of:
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 70, National Electrical Code.
Factory Mutual (FM)
The controller shall be listed by:
Underwriters Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls
Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (cUL)

Enclosure
The controller components shall be housed in a NEMA Type 1 (IEC IP20) drip-proof,
wall mounted enclosure with bottom entry gland plate.

Operation
The alarm panel shall have individual LED lights to indicate its alarm condition which shall remain lighted until the alarm condition has been corrected. The alarm panel
shall also have an audible alarm which will sound when the alarm conditions occur and may be silenced by pressing a SILENCE ALARM push-button. Each alarm initiation shall be subsequent to any and all previous alarm conditions
so that the silence push-button acknowledgment of any one alarm will not prevent the audible alarm from sounding on successive alarm conditions. The alarm panel shall have a PUSH-TO-TEST push-button for manually testing all
LED lights, audible alarms and output circuits. All alarm LED’s and push-buttons shall be plainly marked for identification.

Manufacturer
The alarm panel shall be a Firetrol model FTA200-A for use with electric fire pump controllers, FTA200-AA for use with 2 electric fire pump controllers or model FTA200-F for use with diesel engine fire pump controllers, FTA200-FF for use with 2 diesel engine fire pump controllers or a FTA200-AF for use with 1 electric fire pump controller and 1 diesel engine fire pump controller.

Features

  • Supervisory Power On
  • Power/Phase Failure
  • Phase Reversal
  • Pump Room Alarm
  • Motor Trouble
  • Motor Running

Applications

  • Security command centers in high-rise buildings and commercial complexes.

  • Engineering or facility management offices located away from the pump room.

  • Guardhouses at industrial plant entrances.

  • Any installation requiring NFPA 20 compliant remote monitoring of fire pumps.