FCON 2000 Series Digital Mass Flow Controller

Built-in display setting unit, setting control is possible only with the main unit. Driving power is DC24V single power supply (AC adapter can also be used).

Description

Built-in display setting unit, setting control is possible only with the main unit. Driving power is DC24V single power supply (AC adapter can also be used). Digital communication: RS485 communication. Analog signal: 0-5V and 4-20mA can be switched. Equipped with accumulation function / abnormal flow rate alarm function.

Mass flow Controller controls the gas flow automatically by an electric signal. In order to control the flow rate by measuring mass of a gas, corrections of ambient temperature or use pressure is not required. It uses a variety of process such as semiconductor, flat panel display, solar cell panel, that is required high accuracy. However, our products can be used any process, for example, it can be used in industries such as gas filling, gas welding, sintering, vapor deposition, coating, film formation, optical fiber, analysis,environment related equipment.

The following can be produced and provided for signal cables and AC adapters for drive power.

  • Digital communication cable: (RJ11)-(RJ11) (Please contact us for recommended products.)
  • Analog communication cable: (Half pitch 20-pin connector)-(Terminal treatment) (Please contact us for recommended products.)
  • AC power supply adapter: +24 VDC (DC 22.8 to 25.2 V, 500 mA or more)
  • Digital communication cable for main unit and PC connection (RJ11)-(converter)-(USB) and application software.

Brand

FCON

FCON

We aim to become a company that is continually welcomed by society by providing products and services based on unique technology and new value creation. FCON main business is design development, manufacture and sale of mass flow controllers and their applied products.

Features

  • Built-in display setting unit, setting control is possible only with the main unit.
  • Driving power is DC24V single power supply (At least 500mA AC adapter can also be used).
  • Compact size to realize small size and space saving.
  • Easy installation to various equipment.
  • Digital communication: RS485 communication.
  • Analog signal: 0-5V and 4-20mA can be switched.
  • Equipped with an abnormal flow rate alarm function.
  • Equipped with accumulation function.
  • PC Control Application Software (Optional offer).

Applications

  • Various Gases (Please consult about corrosive gas)

Specifications

Mass Flow Controller C2005 C2020
Mass Flow Meter M2005 M2020
Flow range (N2equivalent) 10,20,30,50,100,200,300,500SCCM
1,2,3,5SLM
10SLM new20SLM
Gases Various Gases (Please consult about corrosive gas)
Valve type NC : Normally Close (Excluding Mass Flow Meter)
Flow rate control range 2-100% F.S (Excluding Mass Flow Meter)
Accuracy ±1% F.S (Accuracy guaranteed between 15-35℃)
Setting signal Setting section of main unit, Digital: RS485, Analog: 0-5V and 4.3-20mA can be switched
(Excluding Mass Flow Meter)
Output signal Main unit display: 7 segment LED, Digital: RS485, Analog: 0-5V and 4-20mA can be switched
Repeatability ±0.2% F.S
Response ≦2sec
Operating differential pressure 50-300KPa 100-300KPa 200-300KPa
Pressure resistance 1MPa(G)
Operating temperature 5-50℃, ≦85%RH (Scope of accuracy guarantee : 15-35℃)
Leak integrity 1×10-7Pa・m3/sec He
Mounting attitude Free
Drive power source +24VDC: ≧500mA
Communication RS485, Analog: 0-5V and 4-20mA can be switched
Wetted surface material SUS316, PTFE, Fluoro-Rubber
Seal material Fluoro-Rubber
Actuator system Solenoid (excluding Mass Flow Meter)
Surface treatment Machined finish
Standard fitting 1/4in.SWL (equivalent), One-touch fittings,  ※ For other fitting, please contact us.
Accessory User’s manual, Written guarantee

Couldn’t find what you were looking for?

Contact us with your specification for assessment and availability of other products configurations.

Click Here