EGE IO-Link Flow sensors SDNC 500

DNC 500 sensors with IO-Link function are the smart solution for process monitoring.

Description

SDNC 500 sensors with IO-Link function are the smart solution for process monitoring. They can measure the flow speed and temperature in fluid mediums. To do so, there is a configuration software which configures the sensors via an IO-Link / USB master. The models …GAPL provide flow data for water-based mediums as as linear otuput signal.

Brand

EGE-Elektronik

EGE-Elektronik

EGE-Elektronik Spezial-Sensoren GmbH has been developing and manufacturing special purpose sensors for automation applications since 1976. The company serves leading international producers from a wide range of industries. Its product portfolio includes flow controllers, infrared, opto and ultrasonic sensors, capacitive proximity switches, light barriers and inductive proximity switches. EGE also provides sensors for highly sensitive applications, e. g. hazardous areas. The development department`s highly qualified staff cooperates closely with all customers, ensuring continuous product updates and enhancement.

EGE has been a pioneer in the field of flow controller and an innovator and decisive participant in the development of today's globally utilized thermal flow controllers. The in-house EMC and test laboratories ensure that all inspections and tests required for permits and conformity certificates are carried out quickly and reliably. Product quality is guaranteed with a continuously monitored quality management system in accordance with EN ISO 9001:2000.

Features

  • Flow and temperature measurement
  • Easy configurable via IO-Link interface
  • Process data can also be used for remote maintenance
  • Analog and switching output in SIO-mode available

 

Applications

SDNC 500 sensors with IO-Link are the smart solution for process monitoring. They can measure the flow speed and temperature in fluid mediums. To do so, there is a configuration software which configures hte sensor via an IO-Link / USB master. The models …GAPL provide flow data for water-based mediums as an linear output signal.

Specifications

ID-No.P11376P11378P11380
TypeSDNC 503 GANPLSDNC 506 GANPLSDNC 508 GANPL
Measuring tube Ø D        [mm]3.55.57.5
Process data
Flow                            [Steps]0…10230…10230…1023
Temperature            [°C x 0.1]0…6000…6000…600
Detection range
Water-based media   [l/min]0.020…0.5000.05… 2.000.10… 4.000.20… 8.00
Resolution                     [l/min]0.0010.010.020.05
ID-No.P11381P11375P11377P11379
TypeSDNC 502 GAPLSDNC 503 GAPLSDNC 506 GAPLSDNC 508 GAPL
Measuring tube Ø D        [mm]3.53.55.57.5
Process data
Flow                 [l/min x 0.001]0…500
[l/min x 0.01]0…2000…4000…800
Temperature            [°C x 0.1]0…6000…6000…6000…600
Adapter L                        [mm]282828100
Supply voltage                   [V]18…30 DCIO-Link-Specifications
Current consumption      [mA]≤40Revision1.1
Switching output             [mA]150 (25 °C)Baud rateCOM 2
Analog output                  [mA]4…20Minimum cycle time    [ms]3.50
Ambient temperature        [°C]0…60Process data            [Byte]4
Medium temperature        [°C]0…60
Reaction time 1                                   [s]0,5
Compressive strength     [bar]10
Sensor materialAISI 316 Ti
Housing materialPBT-GF30
Protection             [EN 60529]IP 67
ConnectionM12 connector
depending on medium and
on operation parameters
Accessories (Selection)CableMounting bracketIO-Link / USB master set
ID-No.Z00446Z01215Z01216
TypeSLW 4-2Mounting bracketIOL-Master-Set V1.1
DesignCable plug housing
M12x1
2 m PVC-cable 4×0.25 mm²
Bracket 37 x 25 x 26 mm (W x L x H)
Aluminium
IO-Link-Master Connection cables Power supply