EGE IO-Link-Devices Programmable air flow sensor LDN 1000

EGE IO-Link-Devices Programmable air flow sensor LDN 1000

Description

The LDN 1009 GAPL detects air flow and temperature in compressed air networks. It display current air consumption of a connected tool or system component in an easy-to-read display and responds quickly to any changes in flow speed. At the same time, the sensor can be used to measure air consumed in standard litres or standard cubic metres.

Brand

EGE-Elektronik

EGE-Elektronik

EGE-Elektronik Spezial-Sensoren GmbH has been developing and manufacturing special purpose sensors for automation applications since 1976. The company serves leading international producers from a wide range of industries. Its product portfolio includes flow controllers, infrared, opto and ultrasonic sensors, capacitive proximity switches, light barriers and inductive proximity switches. EGE also provides sensors for highly sensitive applications, e. g. hazardous areas. The development department`s highly qualified staff cooperates closely with all customers, ensuring continuous product updates and enhancement.

EGE has been a pioneer in the field of flow controller and an innovator and decisive participant in the development of today's globally utilized thermal flow controllers. The in-house EMC and test laboratories ensure that all inspections and tests required for permits and conformity certificates are carried out quickly and reliably. Product quality is guaranteed with a continuously monitored quality management system in accordance with EN ISO 9001:2000.

Features

• Mass flow measurement of air
• Consumption measurement in compressed air networks
• Easy configuration via IO-Link interface
• User levels configurable
• Manipulation detection

Applications

The LDN 1009 GAPL detects air flow and temperature in compressed air networks. It displays current air consumption of a connected tool or system component in an easy-to-read- display and responds quickly to any changes in flow speed. At the same time, the sensor can be used to measure air consumed in standard litres or standard cubic metres.

Specifications

  • Detection ranges
  • Air flow [Nm3/h] :  0.04…15.00
  • [Nl/min] : 0.5…250.0
  • [Nm/s] : 0.2…65.5
  • Temperature [°C] : 0.0…60.0
  • ID-No. : P11373
  • Type : LDN 1009 GAPL
  • Flow deviations
  • from measurement value [±%]  :4
  • from measurement range end value [±%] : 0.5
  • Reproduceability [±%] : 2
  • Temperature deviation 1 [±°C] : 2
  • Output S1 : PNP-NO/NC, NPN-NO/NC, IO-Link, pulse PNP-NO
  • Output S2 : PNP-NO/NC, NPN-NO/NC, Analog 4…20 mA, reset input for dosage
  • Supply voltage [V] : 18…30 DC
  • Current consumption max. [mA] : ≤120
  • Switching current [mA] : ≤150
  • Ambient temperature [°C] : – 10…+60
  • Medium temperature [°C] : 0…+60
  • Start-up time [s] : < 10
  • Reaction time [s] : < 0.3
  • Compressive strength [bar] : 16
  • Sensor material : Aluminium, AISI 304, thermoplast, ceramic, glass coating
  • Housing material : Aluminium, PBT, polyester, AISI 316 Ti
  • Display flow : 6-digit, 7-segment red
  • Protection [EN 60529]  : IP 54
  • Connection : M12 connector
  • Programmable functions : Operating modes: Hysteresis function, window function,
    fault monitoring, pulse output, analog output, dosage function
    Extended functions: Min/ Max/ average value memory,
    customised ID, display configuration, selectable units of 1 Flow rate min. 20%
    of full range measurement and standard values, access restrictions
  • EGE-Elektronik Spezial-Sensoren GmbH • http://www.ege-elektronik.com